before working on the distribution board. Mount the device onto a standard 35mm DIN rail.
Press and hold the button for 3 seconds to enter configuration mode.
If no buttons are pressed for 10 seconds, the device saves all changes and exits to the main screen. Code Setting Matrix Adjustable Range Default Factory Value Power-On Delay Time 1 second ~ 500 seconds 10 seconds A2 Over-Voltage Protection Action Value 221V ~ 300V (or OFF) A3 Over-Voltage Recovery Voltage 220V ~ 299V A4 Over-Voltage Protection Action Time 0.1 second ~ 10 seconds 0.1 second A5 Under-Voltage Protection Action Value 150V ~ 219V (or OFF) A6 Under-Voltage Recovery Voltage 151V ~ 220V A7 Under-Voltage Protection Action Time 0.1 second ~ 10 seconds 0.1 second A8 Over-Current Protection Action Value 1A ~ 63A (or OFF) A9 Over-Current Protection Action Time 0.1 second ~ 50 seconds A10 Fault Recovery Delay Time 1 second ~ 500 seconds 30 seconds A11 Reset Type Mode AU (Auto Reset) / HA (Manual Reset) Safety Guidelines & Troubleshooting
: For broader installation and safety guidelines, you can visit the SINOTIMER User Guides at Manuals+ Quick Setup Guide To adjust the settings on your SVP-916: Enter Setup : Press and hold the button for 3 seconds. Navigate Parameters sinotimer svp916 manual version pdf full
to the bottom terminals marked OUT (L) and OUT (N) .
If under-voltage action time is set higher than , the relay may fail to drive due to MCU power loss. Safety Note: The neutral (
This public link is valid for 7 days and shares a thread, including any personal information you added. This link or copies made by others cannot be deleted. If you share with third parties, their policies apply. Can’t copy the link right now. Try again later. before working on the distribution board
Press and hold the "Set" key for ~3 seconds until the display flashes.
The Sinotimer SVP‑916 is a sophisticated, highly capable voltage protector, but its full potential can only be unlocked through its official documentation. The manual provides not only the parameter programming codes and wiring diagrams but also the critical safety warnings that keep you, your family, and your equipment safe.
Press once to save the parameter and advance to the next code. If no buttons are pressed for 10 seconds,
Connect the live load wire to the terminal marked OUT L . Connect the neutral load wire to the terminal marked OUT N .
: Power is restored automatically once the line voltage stabilizes, with a configurable delay time (2s–512s).